Error message
- Deprecated function: The each() function is deprecated. This message will be suppressed on further calls in book_prev() (line 775 of /usr/share/nginx/html/sanchitha.lsgkerala.gov.in/modules/book/book.module).
- Deprecated function: implode(): Passing glue string after array is deprecated. Swap the parameters in drupal_get_feeds() (line 394 of /usr/share/nginx/html/sanchitha.lsgkerala.gov.in/includes/common.inc).
Section 111
- The wiring for the open yard lighting shall be done with weather-proof wires of suitable size according to the load of the current in that circuit, threaded through porcelain reel insulators suspended from suitable bearer wires at a height not less than four metres from ground level. The reel insulators shall be spaced 50 centimetres from each other.
- When a tapping is taken from the open yard wiring it should be taken only a point of support through porcelain connectors housed in a junction box fixed to the supporting pole. In the case of service it should be taken through a lead in pipe.
- Supply to the lights in the open yard shall be tapped from the junction boxes as above and the light brackets shall be fixed on a separate round block fixed to the supports. The wires from the junction box to the light brackets should be enclosed in earthed conduit pipes similar to the method adopted for the street light fixtures.