Section 110
- The Licensee shall ensure that the installation conforms to the provisions of Indian Electricity Act, 1910 and Indian Electricity Rules, 1956 in the matter of entire electrical installation.
- Separate permanent circuit should be wired up with suitable switch fuse control; for the outdoor wiring, switched outlets of 3 pin type with metal clad, water tight socket outlet should be located at convenient places at suitable heights from where supply line may be taken out, by using weatherproof wires for the display lights similar to yard lighting.
- The outdoor lighting fitting should be water tight type.
- The electrical installations both in the auditorium and the projection room in the same theatre shall be done only in conduit.
- All the electrical apparatus, main and sub distribution boards, metal clad switches and the earth leads of the circuits shall be effectively earthed. A minimum of two earth electrodes has to be provided for a Theatre, conforming to the provisions of I.S.I. Standard in this respect.