Section 109

  1. The electric lighting of the premises shall have at least three separate distinct main circuits as follows:

    1. for the projection room and thence through a dimming regulator to the central lighting of the auditorium.
    2. for approximately one-half of the auditorium, passage ways, stairways, exits and parts of the building open to the public; and
    3. for the remaining half of the auditorium, passage ways, stair-ways, exits and pans of the building open to the public The control of the circuit in respect of the two halves of the auditorium referred to in clauses (b) and (c) shall be remote from each other.
  2. A plan (in single line) of the wiring shall be kept in a prominent place in the office of the Manager.
  3. Sufficient number of emergency lights shall be provided in the auditorium as prescribed by the Licensing Authority.
  4. No open flames shall be allowed within the auditorium or in the projection room.